E6581741h
TOSVERT VF-MB1/S15
EtherNet/IP™ - Modbus
®
TCP option
Function Manual
IPE002Z
NOTICE
1. Read this manual before installing or operating. Keep this instruction manual on hand
of the end user, and make use of this manual in maintenance and inspection.
2. All information contained in this manual will be changed without notice. Please
contact your Toshiba distributor to confirm the latest information.
Przeglądanie stron 0
1 2 3 4 5 6 ... 88 89

Podsumowanie treści

Strona 1 - E6581741h

E6581741h TOSVERT VF-MB1/S15 EtherNet/IP™ - Modbus® TCP option Function Manual IPE002Z NOTICE 1. Read th

Strona 2 - Caution

E6581741 - 9 - Title Communication No. Function Description Factory settingc500 C500 Protocol (*3) This parameter is used to set the protocol of th

Strona 3 - Table of Contents

E6581741 - 10 - EtherNet/IP parameters Title Communication No. Function Description Factory settingc536 C536 EtherNet Error Monitor of the EtherNet

Strona 4

E6581741 - 11 - 3.2. The details of the parameter setting 3.2.1. Device name (c081-c096) This option module can set the "Device name" o

Strona 5 - 2. Names and functions

E6581741 - 12 - 3.2.2. Assigning IP addresses (c504, c505-c516) The drive needs 3 (4-Modbus TCP) IP addresses. *The drive IP address. *The subnet m

Strona 6

E6581741 - 13 - 3.2.3. Network error detection (c100 - c103, c523) ▼Display of trip information err8 (Optional unit fault 1: 1BH): Network error st

Strona 7 - 2.4. LED indicator

E6581741 - 14 - 3.2.4. Command data (c001-c006), Monitor data (c021-c026) The outline is indicated about the setting item of parameter c001 – c006 a

Strona 8 - 3. Parameters

E6581741 - 15 - 3.2.4.2. fa06 (Communication command1) bit Function 0 1 Note 0 Preset speed operation frequencies 1 1 Preset speed operation fr

Strona 9

E6581741 - 16 - 3.2.4.3. fa23 (Communication command 2) bit Function 0 1 Note 0 (Reserved) - - - 1 Electric power quantity reset OFF Reset E

Strona 10 - E6581741

E6581741 - 17 - 3.2.4.4. fa07 (frequency reference from internal option) Frequency reference is set up by 0.01Hz unit and the hexadecimal number.

Strona 11 - Warning

E6581741 - 18 - 3.2.4.7. fd01 (Inverter operating status 1) bit Function 0 1 Note 0 Failure FL No output Under in progress - 1 Failure Not t

Strona 12

E6581741 - 1 - - 1 -Introduction Thank you for purchasing the “EtherNet/IP™ - Modbus® TCP option (IPE002Z)” for TOSVERT VF-MB1/S15 inverter. Before

Strona 13

E6581741 - 19 - 3.2.4.9. fd03 (Output current) The output current is read into 0.01% of units and by the hexadecimal number. For example, when t

Strona 14

E6581741 - 20 - 3.2.4.13. fc91 (Alarm code) bit Function 0 1 Remarks (Code displayed on the panel) 0 Over-current alarm Normal Alarming c flickin

Strona 15

E6581741 - 21 - 3.2.4.15. fd07 (Output TB Status) bit TB Name Function (Parameter) 0 1 0 RY-RC Output terminal function selection 1A (f130

Strona 16

E6581741 - 22 - 4. Objects This section contains the object specifications for all EtherNet/IP objects currently supported by the “IPE002Z”. Table 1

Strona 17

E6581741 - 23 - 4.1. Identity Object (0x01) Class code 0x01. This object provides identification of and general information about the device. C

Strona 18

E6581741 - 24 - Attribute 5 State Descriptions Adapted from document [CIP] “THE CIP NETWORKS LIBRARY” Bit Called Definition 0 Owned TRUE indicat

Strona 19

E6581741 - 25 - 4.2. Message Router Object (0x02) Class code 0x02. The Message Router Object provides a messaging connection point through which

Strona 20

E6581741 - 26 - 4.3. Assembly Object (0x04) Class code 0x04. The Assembly Object binds attributes of multiple objects, which allows data to or fr

Strona 21

E6581741 - 27 - 4.4. Connection Manager Object (0x06) Class code 0x06. Use this object for connection and connectionless communications, includ

Strona 22

E6581741 - 28 - 4.5. Motor Data Object (0x28) Class code 0x28. This object serves as a database for motor parameters. Class Attributes Instance

Strona 23 - 4. Objects

E6581741 - 2 - Table of Contents 1. OVERVIEW ...

Strona 24 - 4.1. Identity Object (0x01)

E6581741 - 29 - 4.6. Control Supervisor Object (0x29) Class code 0x29. This object models all the management functions for devices within the “Hi

Strona 25

E6581741 - 30 - Instance Services Service Code Service Name Description of Service 0x05 Reset Resets the drive to the start-up state. 0x0E G

Strona 26

E6581741 - 31 - 4.6.1. Run/Stop Event Matrix Run1 Run2 Trigger Event Run Type 0 0 Stop No Action 0 -> 1 0 Run Run1 0 0 -> 1 Run Ru

Strona 27 - 4.3. Assembly Object (0x04)

E6581741 - 32 - 4.7. AC/DC Drive Object (0x2A) Class code 0x2A. This object models the functions specific to an AC or DC Drive. e.g. speed ramp,

Strona 28

E6581741 - 33 - 4.8. Parameter Objects (0x64) Class code 0x64. This object provides VF-MB1/ S15’s Parameter access. Range Address accessed: Input

Strona 29

E6581741 - 34 - Instance Services Service Code Service Name Description of Service 0x0E Get_Attribute_Single Read one attribute 0x10 Set_Attribu

Strona 30

E6581741 - 35 - 4.9. Parameter Objects (0x65) Class code 0x65. This object provides VF-MB1/S15’s Parameter access. Range Address accessed: Input In

Strona 31

E6581741 - 36 - 4.10. Port Object (0xF4) Class code 0xF4. The Port Object enumerates the CIP ports present on the device. One instance exists for

Strona 32 - 4.6.2. State of the drive

E6581741 - 37 - 4.11. TCP/IP interface Object (0xF5) Class code 0xF5. The TCP/IP Interface Object provides the mechanism to configure a device’s TCP

Strona 33

E6581741 - 38 - Instance 1 Attribute Instance Attribute ID Access Name Data type Details 1 Get Status DWORD Bits 0 -3 : Interface configurat

Strona 34

E6581741 - 3 - 8.7. "23 (0x17) Read/Write Multiple Registers" function...

Strona 35

E6581741 - 39 - Instance Attribute ID Access Name Data type Details Mcast Config STRUCT of IP Multicast address configuration Alloc Config US

Strona 36

E6581741 - 40 - 4.12. Ethernet link object (0xF6) Class code 0xF6: The Ethernet Link Object maintains link-specific counters and status information

Strona 37 - 4.10. Port Object (0xF4)

E6581741 - 41 - Instance 1 Attribute Instance Attribute ID Access Name Data type Details 1 Get Interface Speed UDINT Interface speed currently

Strona 38

E6581741 - 42 - Instance Attribute ID Access Name Data type Details Media Counters STRUCT of Media-specific counters Alignment Errors UDINT

Strona 39

E6581741 - 43 - Instance 2 Attribute Instance Attribute ID Access Name Data type Details 1 Get Interface Speed UDINT Interface speed currently

Strona 40

E6581741 - 44 - 5. Configuration of the assemblies 5.1. List of Assembly Object Instance Output Instance Instance name Number (Hex) Size CIP ba

Strona 41

E6581741 - 45 - 5.1.1. Instance 20: CIP basic speed control output Instance 20 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0

Strona 42

E6581741 - 46 - 5.1.3. Instance 21: CIP extended speed control output Instance 21 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Strona 43

E6581741 - 47 - 5.1.5. Instance 100: Native drive output Instance 100 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 DC brakin

Strona 44

E6581741 - 48 - Examples of Instance 100/150 ① Stop Instance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex. 1, 0 0 0 00000000000 0 0 0 0x

Strona 45 - Input Instance

E6581741 - 4 - 1. Overview The EtherNet/IP™ - Modbus® TCP option (IPE002Z) allows the VF-MB1/S15 inverter to be connected into the EtherNet/IP™ - Mo

Strona 46

E6581741 - 49 - 5.1.7. Instance 101: Native drive output Instance 101 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 - Net Ref

Strona 47

E6581741 - 50 - Examples of Instance 101/151 Access the inverter parameter is enabled using byte 4 to 6 of this Instance. Set the communication nu

Strona 48

E6581741 - 51 - 5.1.9. Instance 102: Native drive output Instance 102 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 c001 Com

Strona 49

E6581741 - 52 - 5.1.11. Instance 105: TOSHIBA specific output Instance 105 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 1 F

Strona 50

E6581741 - 53 - Examples of Instance 105/155 Access the inverter parameter is enabled using byte 1 to 5 of this Instance. Set the communication nu

Strona 51

E6581741 - 54 - 6. About EDS file As for acquisition of an EDS file for VF-MB1 and VF-S15, please contact your Toshiba distributor. 7. Integratio

Strona 52

E6581741 - 55 - 7.2. Add a EtherNet/IP scanner to the I/O configuration Right-click the I/O Configuration, and select “New Module”.

Strona 53

E6581741 - 56 - Select the Module as below. Select revision of drive. Put in Name and IP address, and press “OK” button.

Strona 54

E6581741 - 57 - 7.3. Configure the VF-MB1/S15 EtherNet/IP module Right-click the EtherNet/IP scanner, and select “New Module”.

Strona 55 - 7. Integration in RSLogix™

E6581741 - 58 - Above the Allen-Bradley drive profile is selected. Select the format of the data. Above the CIP basic speed control

Strona 56

E6581741 - 5 - 2.2. RJ45 connector pin layout The EtherNet/IP™ - Modbus® TCP option is equipped with two shielded RJ45 connectors. When you use VF

Strona 57

E6581741 - 59 - 7.4. Download the program to the PLC The first download follows the following procedure. Select the using

Strona 58

E6581741 - 60 - Select the "Download." Once again, select the "Download."

Strona 59

E6581741 - 61 - 7.5. Edit the I/O scan data Open the "Controller Tags." Set to the "Offline" if change the

Strona 60

E6581741 - 62 - Download the changed data to the PLC. : "Communications" J "Download" After the setting i

Strona 61

E6581741 - 63 -

Strona 62 - 7.5. Edit the I/O scan data

E6581741 - 64 - 8. Modbus TCP server 8.1. Modbus TCP frames Modbus TCP frames consist of a header and a Modbus request. Header format: Byte Descr

Strona 63

E6581741 - 65 - 8.4. "03 (0x03) Read Holding Registers" function The Modbus request is used to read the values of a number (No. of Points

Strona 64

E6581741 - 66 - 8.5. "06 (0x06) Write Single Register" function This Modbus request is used to write a given value (Present Data) to the

Strona 65 - 8. Modbus TCP server

E6581741 - 67 - 8.6. "16 (0x10) Write Multiple Registers" function This Modbus request is used to write a number (No. of Registers) of ad

Strona 66

E6581741 - 68 - 8.7. "23 (0x17) Read/Write Multiple Registers" function The "Read/Write Multiple Registers" service is reserved

Strona 67

E6581741 - 6 - 2.4. LED indicator The LED shows the present status of the network and module. The behavior of LNK LED Link Activity Protocol

Strona 68

E6581741 - 69 - 8.8. "43 (0x2B) Read Device identification" function The "Read/Write Multiple Registers" service is reserved fo

Strona 69

E6581741 - 70 - Response format: (ID = 251) Byte Meaning With the IPE002Z 0 Function Code = 2Bh 2Bh 1 Type of MEI 0Eh 2 Read Device ID code

Strona 70

E6581741 - 71 - 8.9. Parameter data It is explanation by the reference method of the list of parameters of the VF-MB1 or VF-S15 series as follows. F

Strona 71

E6581741 - 72 - 9. IO Scanning service 9.1. Presentation The IO Scanning service is used to exchange I/O data between:  A controller or PLC (IO Sc

Strona 72 - 8.9. Parameter data

E6581741 - 73 - 10. Example of the setup with PL7™ It is an example of the setup using PLC (PL7™) made by Schneider electric as follows. 10.1. Def

Strona 73 - 9. IO Scanning service

E6581741 - 74 - 10.2. BOOTP configuration The BOOTP server function consists of allocating BOOTP clients their IP addresses. The activation conditio

Strona 74

E6581741 - 75 - 10.3. Configuring Modbus messaging To use Modbus messaging in PL7, the “IP address”, “Subnet mask” and “Gateway address” parameters

Strona 75 - 10.2. BOOTP configuration

E6581741 - 76 - 10.4. Configuring periodic variables This window is used to configure the IO Scanning function, described in the IO Scanning Service

Strona 76

E6581741 - 77 - 11. Command & Setpoint selection (Local/Remote) Indication to display Local/Remote mode is on the inverter unit (Refer to the i

Strona 77

E6581741 - 78 - <Example of setting> The example below shows how to configure the local/remote operation. F terminal ... Operatin

Strona 78

E6581741 - 7 - 3. Parameters 3.1. Communication parameters Set up the inverter parameters as follows. It is necessary to reset the inverter to upd

Strona 79 - EtherNet/IP-Modbus TCP

E6581741 - 79 - 12. Unusual diagnosis 12.1. Option error An error message is displayed when the hardware error or software error or lose of connect

Strona 80 - 12. Unusual diagnosis

E6581741 - 80 - 13. WebServer The option has webserver function. Writing and reading the drive's parameter and the communication can be monito

Strona 81 - 13. WebServer

E6581741 - 81 - From the TOSVERT home page, you can access to 3 main menus:  Monitoring  Network setup  Diagnostics 13.2. Web

Strona 82 - 13.2. Web pages structure

E6581741 - 82 - 13.3. Drive monitor (Main menu: Monitoring) The state of the drive can be confirmed on this page.

Strona 83

E6581741 - 83 - 13.4. Drive parameters (Main menu: Monitoring) The parameters of the drive can be set on this page. The left column is used to selec

Strona 84

E6581741 - 84 - Input the write value to popup window.

Strona 85

E6581741 - 85 - 13.5. Network parameters (Main menu: Network Setup) The network parameters of the drive can be confirmed on this page.

Strona 86

E6581741 - 86 - 13.7. EthIP scanner (Main menu: Network Setup) The I/O scanner of the EtherNet/IP protocol can be set on this page.

Strona 87

E6581741 - 87 - 13.8. Administration (Main menu: Network Setup) The "web read password" and "web write password" of the webserve

Strona 88

E6581741 - 88 - 13.9. TCP/IP statistics (Main menu: Diagnostics) You can check TCP/IP status on this page. - 88E-

Strona 89

E6581741 - 8 - Title Communication No. Function Description Factory settingc021 C021 Scanner output 1 address (*3)0: - 1: fd01 (Status informatio